Resistive load banks
Big resistor grids that convert the generator’s output to heat — the standard tool. Sized to the set (a 500 kW bank for a 500 kW set), connected at the generator or transfer switch, run through stepped load profiles: 25/50/75/100% and back down.
What gets verified
Voltage and frequency regulation under load, transient response (the dip and recovery when load steps on), cooling system capacity at full heat, fuel system under full flow, and whether the set actually makes nameplate kW. A set that cannot hold rated output on the bank cannot hold it in the outage.
Reading the report
A proper report shows load steps, voltage/frequency at each step, oil/coolant/exhaust temps, and fuel consumption — with pass/fail against the manufacturer’s spec. When buying used, this report is the machine’s résumé: recent, loaded, documented. No report? Price accordingly.