Standby vs. Prime vs. Continuous.

The three ratings that decide what a generator is allowed to do — and the distinction the used market turns on.

Sell Your Generator

STANDBY~200 hr/yr PRIMEUNLIMITED VAR CONTINUOUS24/7 CONSTANT MATCH THE RATING TO THE DUTY
DUTY RATING LADDERGEN HUB PLATE 3 OF 10
RATINGS

Three ratings, three different machines.

Every industrial generator carries an ISO 8528 duty rating — standby, prime, or continuous — and the rating decides what the machine is legally and mechanically allowed to do. Buyers who ignore it buy a standby set for prime duty and kill it in two years. Sellers who state it correctly sell faster. This is the distinction the whole used market turns on.

Know your rating?

It’s on the nameplate — photograph it when you sell. Sell your generator →

THE THREE

Standby, prime, continuous

RatingISO 8528Allowed useOverloadTypical hours/yr
Standby (ESP)Emergency Standby PowerBackup during utility outage onlyNone~200
Prime (PRP)Prime Rated PowerPrimary power, variable load, unlimited hours10%, 1 hr in 12Unlimited
Continuous (COP)Continuous Operating PowerConstant load, unlimited hoursNoneUnlimited (8,760)

The same physical machine often carries three different numbers — e.g. 100 kW standby / 90 kW prime / 80 kW continuous. The derate between them is the manufacturer telling you how hard each duty cycle is on the machine. A listing that says “100 kW” without the rating is hiding the only number that matters for your application.

IN PRACTICE

What each rating means for you

Standby: the backup

For outages — hospitals, data centers, commercial buildings with utility service. Runs occasionally, must start fast and carry full load immediately. Never run a standby set as primary power: no overload allowance and ~200 hrs/year design life means prime duty destroys it. Most used sets on the market are standby — low hours, clean, and exactly right for backup.

Prime: the workhorse

For off-grid sites, construction, oil & gas, events — anywhere the generator is the utility. Unlimited hours at varying load, with a 10% overload allowance one hour in twelve. Prime sets are built heavier (cooling, bearings, alternator) and priced accordingly. If your application runs daily, you need prime — a standby set will not survive it.

Continuous: the baseload

Constant load, 24/7 — cogeneration, peak shaving, remote facilities. No overload, ever: the rating assumes the machine never gets a break from full load. The most conservative rating — and the one that commands the most respect from buyers who know, because a continuous-rated set at its rating will run for decades.

BUYING & SELLING

The rating is the listing

When buying used: match the rating to the duty — standby for backup, prime for daily use. A low-hour standby set is the best value in backup power; a high-hour prime set is a known quantity with maintenance records (or a gamble without them). When selling: state all three ratings from the nameplate. “100 kW standby / 90 kW prime” sells faster and for more than “100 kW generator,” because it tells the buyer you know what you have. The nameplate photo settles every argument.

QUESTIONS

Rating questions, answered.

Can I run a standby generator as prime power?

No — standby sets have no overload allowance and are designed for ~200 hrs/year. Prime duty will destroy a standby set far ahead of its time.

Why does one generator have three kW numbers?

Same machine, three duty cycles: standby (highest — occasional use), prime (middle — daily variable load), continuous (lowest — 24/7 constant load). The derate reflects mechanical reality.

What is the 10% overload on prime ratings?

ISO 8528 allows prime-rated sets 10% overload for 1 hour in every 12 — for transient peaks, not sustained operation.

Which rating holds value best used?

Low-hour standby sets — the most common listing and the cleanest machines. Prime sets hold value with documented maintenance history.

Does the rating affect EPA tier?

Indirectly: emergency standby engines are exempt from Tier 4 Final; prime/continuous (non-emergency) engines are not. See the EPA tiers guide.

HOW IT WORKS

Sell your generator in three steps

1. Photograph it

Nameplate (make, model, kW, serial), hour meter, and overall condition. The nameplate is the entire specification.

3. Get today’s price

A real offer based on your photos and today’s market — not a calculator, not a guess.

GENERATOR RESOURCES

More power knowledge

Sell Your Generator to Ironcrest

Diesel or natural gas, running or parts — send photos for today’s price.

Get Today’s Price Call/Text 312-880-8174