▲ IRONCRESTINDUSTRIALINDUSTRIAL SURPLUS BUYERS
THE WIRE GUIDE — CHICAGO

Romex vs. MC Cable vs. BX: What's the Difference and When to Use Each

Romex, MC cable, and BX all carry the same electricity — but they're built nothing alike. Here's which one goes where, which one costs what, and what the old BX in your Chicago basement actually is.

THE 30-SECOND ANSWER

Three cables, three different jobs

Romex (Type NM-B) is the plastic-sheathed budget option: cheapest, easiest to run, allowed in dry residential interiors — but it has zero physical protection and can't go where it might take abuse. MC (metal-clad) cable wraps the same kind of conductors in flexible interlocked metal armor and carries its own green ground wire inside — it's the commercial workhorse, allowed exposed, concealed, in trays, and in more locations than Romex. BX (Type AC) is the older armored cable: steel armor with a thin bonding strip inside it — the armor plus the strip is the ground path, and there's no separate ground wire in the bundle.

If your Chicago-area house was wired before about 1960, what's in the walls is almost certainly old BX — and the pre-1960 stuff often doesn't even have the bonding strip, which means no real equipment ground at all. The diagram below shows the physical difference. Once you see it, you can't unsee it.

CABLE CROSS-SECTIONS — SHOWN TO SCALE (12-2, APPROX.) ROMEX® / TYPE NM-B 12 AWG black — hot white — neutral bare copper ground flat PVC sheath COST — lowest of the three PROTECTION — sheath only, no armor GROUND — bare copper wire TYPE MC CABLE green insulated ground interlocked aluminum armor THHN conductors COST — more than Romex PROTECTION — metal armor GROUND — green wire (armor is NOT the ground) TYPE AC / "BX" bonding strip (16 AWG) — touches armor steel armor COST — mid, similar to MC PROTECTION — metal armor GROUND — armor + strip (no separate wire) Drawn to scale from 12-2 specimens — outside diameters approximate. 12-2 means two insulated conductors plus ground. 1 inch IRONCREST WIRE GUIDE — PLATE NO. 6
Cable cross-sections to scale: NM-B is flat plastic, MC is armor plus its own ground wire, AC ("BX") is armor plus a bonding strip with no separate ground. The grounding difference is the whole story.
ROMEX — TYPE NM-B

The plastic-sheathed budget option

Romex is Southwire's brand name for Type NM-B (nonmetallic-sheathed cable), and the name stuck to the whole product family. It's a flat PVC jacket wrapped around two or three insulated conductors plus a bare copper ground — 12-2, for example, is black and white 12 AWG with an uncounted bare ground. The conductors inside are insulated to 90°C, but the cable itself must be sized off the 60°C ampacity column (NEC 334.80) — that's why 12-2 Romex is a 20-amp circuit, full stop. Want the full table? Here's the wire gauge chart — what size wire for every amperage.

Where it's allowed: dry, protected residential interiors — inside walls, above ceilings, through bored holes in studs. Where it's not: anywhere it might take physical damage, in wet or damp locations, or run exposed where the code requires protection. It's the cheapest of the three by a wide margin and the fastest to pull, which is why it's the default house wire everywhere the code allows it.

One Chicago-specific catch: the city of Chicago has long restricted NM cable to temporary and very limited uses in its electrical code amendments, favoring EMT conduit. Out in the suburbs — Rolling Meadows, Schaumburg, Palatine, Elgin — Romex follows the NEC and is the normal residential wiring method.

MC CABLE — TYPE MC

The metal-clad middle ground

Metal-clad cable (NEC Article 330) is flexible interlocked metal armor — usually aluminum, sometimes steel — wrapped around THHN-type insulated conductors. The standard 12-2 MC has black, white, and a full-size green insulated ground wire inside the armor. That green wire is the equipment ground. Here's the part people get wrong: on standard interlocked MC, the armor itself is not the grounding path (NEC 250.118(10)) — the green wire is, and the armor is bonded through listed fittings as a supplement.

MC is allowed in far more places than Romex: exposed and concealed work, cable trays, and — with listed PVC-jacketed types — damp and wet locations. It costs more than Romex and takes proper MC connectors and a rotary cutter to terminate right, but on commercial jobs and Chicago-area retrofits where conduit isn't practical, MC is the standard answer. Electricians know it; inspectors know it; it passes without drama.

AC CABLE — "BX"

The old armored cable in half the city's walls

Type AC — armored cable, NEC Article 320 — is what everyone calls BX. BX was originally a manufacturer's trade name for early armored cable; the name stuck and became generic. Modern AC is interlocked steel armor around two to four conductors (14 AWG up to 1 AWG), with a 16 AWG bonding strip running in constant contact with the inside of the armor for the cable's entire length.

That bonding strip is the whole grounding story: the armor plus the strip is the equipment ground (NEC 250.118(8)) — there is no separate ground wire in the bundle. When you terminate AC, you cut the strip back and bond the armor through a listed connector. And this is the critical part for old buildings: BX made before roughly 1960 often has no bonding strip at all. No strip, no reliable ground path — the armor alone isn't a code-recognized ground. If you're looking at cloth-wrapped conductors inside old BX in a Chicago bungalow, that's what you're dealing with. AC is never permitted in wet or damp locations, and it's limited to four conductors or fewer.

How to tell AC from MC at a glance: read the jacket. Modern AC is marked TYPE AC with the bonding strip inside; MC is marked TYPE MC and carries a green or bare ground wire. Learn to read the jacket printing here — it settles the argument in ten seconds.

SIDE BY SIDE

The comparison, in one table

—Romex / NM-BMC cableAC / "BX"
Outer layerFlat PVC sheathInterlocked metal armor (aluminum or steel)Interlocked steel armor
CostLowest by a wide marginMid — more than RomexMid — similar to MC
ProtectionNone — sheath onlyMetal armorMetal armor
GroundingBare copper wireGreen insulated wire (armor is not the ground)Armor + bonding strip (no separate wire)
Where usedDry residential interiorsCommercial, exposed, concealed, trays, some wet locations (listed types)Dry interior branch circuits and feeders
Wet locationsNoOnly listed wet-location typesNo
Conductors2–3 plus ground, many gauges18 AWG and up, many counts2–4 only, 14 AWG–1 AWG
THE CHICAGO NOTE

What you'll actually find around here

Chicago's electrical code has required EMT conduit for most residential wiring for generations — that's why Chicago houses don't have the Romex-in-the-walls look the rest of the country is used to. Open up a pre-1960 Chicago bungalow or two-flat and you'll find old BX everywhere: cloth-wrapped conductors, steel armor, usually no bonding strip, which means no equipment ground — two-prong outlets all the way down.

Out in the suburbs, it's the NEC playbook: Romex in new residential, MC in commercial and retrofit work, old BX still lurking in the older housing stock. If you're pulling old BX out of a rewire — or you bought a job's worth of MC and have reels left — that armored cable has resale value in usable lengths. Pulling out old BX on a rewire or sitting on leftover MC from a job? We buy usable wire rolls — anywhere in the country. Fast, free quote.

FREQUENTLY ASKED QUESTIONS

Romex vs. MC vs. BX questions, answered.

Can I use Romex instead of MC cable?

Wherever the NEC allows NM cable for the application, Romex does the same job for less money — branch circuits in dry, protected residential locations. But it can't replace MC where the code requires protection: exposed runs subject to damage, commercial work, or locations where only a chapter-3 wiring method like MC is permitted. And in the city of Chicago itself, NM is restricted to temporary and limited uses — conduit is the rule there.

Is BX cable the same thing as AC cable?

BX was the original trade name for what the NEC calls Type AC cable. Same product family, same article (NEC 320). In practice, "BX" usually refers to older installations — especially the pre-1960 cable without a bonding strip — while new product is marked and sold as Type AC.

Does MC cable need a separate ground wire?

It comes with one already inside — the green insulated (or bare) equipment grounding conductor. On standard interlocked MC, that green wire is the ground path; the armor itself is not recognized as the equipment ground (NEC 250.118(10)). Terminate it like any other ground wire.

Why does everything in Chicago get wired in conduit?

Chicago's electrical code amendments have restricted NM, AC, and MC cable methods in favor of EMT and other raceways for generations — the reason most often cited is protection against physical (including rodent) damage. The suburbs generally follow the NEC directly, where Romex and MC are normal. Always check the local amendment before pulling cable in the city.

Can MC or BX be run outside or underground?

AC ("BX") is never permitted in wet or damp locations. Standard MC isn't either — but MC types listed for wet locations (PVC-jacketed) are. Neither is a substitute for conduit or direct-burial cable underground. If the run goes outside, use a wiring method listed for the location.

IRONCREST KNOWS WIRE

I know wire. That's how I know what it's worth.

I handle Romex, MC, and BX every week — reading jackets, checking grounds, sorting the usable rolls from the scrap. That's also how I know when good armored cable is worth more than the yard pays for it.

CALLSEND PHOTOS