What Is Armored Cable (AC/BX) and Where Is It Still Used
"BX" is the old trade name for what's technically Type AC cable — and half the older buildings in Chicago are wired with it. Here's what's actually inside the armor, and why one thin strip of metal is the whole story.
Inside the armor: the AC cable cutaway
Type AC cable is four things wrapped together, and each layer has a job:
- The conductors. Modern AC carries THHN/THWN copper singles — usually black and white, sometimes with a red — each individually wrapped in a moisture-resistant, flame-retardant paper. Old BX-era cable used rubber-insulated conductors; the construction has improved, the concept hasn't changed.
- The bonding strip. This is the part most people have never heard of, and it's the whole story. A bare 16 AWG aluminum strip runs the full length of the cable, tucked inside the armor in intimate contact with it (required by NEC 320.100). It shorts out the spiral of the armor so fault current flows instead of choking on the coil's inductance.
- The armor. A flexible steel (or aluminum) tape wound in an interlocking spiral. It takes the physical abuse — nails, abrasion, being fished through old plaster walls.
- The anti-short bushing. A little plastic "redhead" slipped over the conductor ends where they exit the cut armor, required by NEC 320.40 so the sharp edge of the tape can't slice into the insulation.
Here's why the bonding strip matters: the armor of Type AC cable is a recognized equipment grounding conductor (NEC 250.118) — but only the armor plus the bonding strip working together. The strip by itself is not a ground wire, and the armor by itself (on old BX that predates the strip) isn't a listed ground path either. That thin aluminum ribbon is what makes the whole assembly legal as a grounding method. When you terminate AC, you can cut the strip off or fold it back against the armor — you don't land it on a ground terminal like a wire.
"BX" vs. AC: the name and the difference
"BX" is the old trade name for what's technically Type AC cable. Electricians have called it BX for a century; the code calls it AC. The meaningful difference isn't the name — it's the bonding strip. Cable made before the strip became standard (roughly pre-1960s BX) has armor but no bonding strip, and that armor alone doesn't qualify as an equipment grounding conductor under today's code. So when someone says "old BX has no ground," this is what they mean — not that the armor vanished, but that the armor never had its bonding partner.
How to tell what you're holding: cut the armor back (carefully — it's sharp) and look just under it. A thin bare aluminum strip running lengthwise means modern Type AC. No strip means old BX. That one detail changes how an electrician treats the circuit — and it's the kind of thing worth knowing before anyone quotes you a rewire. For the side-by-side with Romex and MC cable, see Romex vs. MC cable vs. BX: what's the difference and when to use each.
Where AC cable is still used
AC never went away — it just stopped being the default. It's still specified and installed today for:
- Commercial and institutional branch circuits — offices, schools, retail, where a little physical protection beats Romex but full conduit is overkill.
- Healthcare facilities — patient-care areas require wiring methods whose outer margin qualifies as an equipment grounding path, and AC inherently qualifies.
- Exposed work and fished retrofits — the armor survives being pulled through old plaster and lath walls, which is exactly why Chicago's rehab electricians reach for it.
- Dry locations, concealed or exposed — AC is a dry-location cable. Wet or damp locations need something else.
The Chicago angle: walk through any pre-1960 bungalow, two-flat, greystone, or vintage commercial building in the city and you're likely looking at AC/BX in the walls — miles of it, most of it installed between the 1920s and the 1960s. When those buildings get gutted and rewired, that old armored cable comes out by the dumpster-load. Most of it is scrap. But the unused coils and partial reels the electricians leave behind are a different story.
Pulling old BX out of a rehab — or sitting on unused AC cable? We buy usable leftover wire — anywhere in the country. Fast, free quote.
Armored cable questions, answered.
What is BX cable?
"BX" is the old trade name for Type AC (armored cable) — insulated conductors inside a flexible interlocked metal armor. The code term is AC; electricians still say BX. Modern AC includes a 16 AWG aluminum bonding strip inside the armor; very old BX doesn't.
Is BX cable grounded?
Modern Type AC is — the armor plus the internal bonding strip together form a recognized equipment grounding conductor (NEC 250.118). Old BX without the bonding strip doesn't have a listed grounding path, which is why electricians treat it differently.
What is the bonding strip in AC cable for?
It's a bare 16 AWG aluminum strip in intimate contact with the armor for its entire length (NEC 320.100). It shorts across the spiral turns of the armor so fault current flows freely instead of being choked by the coil's inductance — that's what makes the armor work as a ground.
Can you still install BX cable today?
Yes — Type AC is a current, listed wiring method for dry locations, and it's still manufactured and installed, especially in commercial work and healthcare facilities. The "BX is obsolete" idea comes from confusing old ungrounded BX with modern AC.
How can you tell AC cable from MC cable?
Cut the armor back and look underneath: AC has the thin bare bonding strip and paper-wrapped conductors; MC has a full-size insulated green (or bare) equipment grounding conductor and no bonding strip. The jacket printing settles it — TYPE AC vs. TYPE MC.
Where is armored cable not allowed?
AC is for dry locations — not wet or damp ones, not where subject to physical damage beyond what the armor handles, and not in corrosive environments unless protected. Local amendments (Chicago's, for example) can add restrictions, so check with the AHJ.
Is old BX wiring dangerous?
Not automatically — but it has no listed grounding path, the rubber insulation is 60+ years old, and decades of amateur taps are common. An electrician's inspection tells you whether it's serviceable or a rewire candidate.